Flange ball valve KFL-B

Technical Description

The KFL-B ball valve consists of a 2-piece body. Up to nominal size DN 100, the flange is screwed into the body. From nominal size DN 125, the two body parts are flanged together. The stem is blowout-proof and, from nominal size DN 32, is fitted with a double O-ring seal. Actuators can be mounted from DN 32 via the standard ISO flange connection.

Technical Data

Design Type

25 – PN 10 to DIN EN 1092-1
26 – PN 16 to DIN EN 1092-1

Connection Types

DIN flange

Nominal diameter

DN 25-200

Material

Ductile cast iron

Pressure Ratings

PN max. 16

Face-to-Face Dimensions

DIN EN 558 FTF basic series 1 (formerly: DIN 3202-1 series F1)

Approvals

Series 26: DVGW for gas PN 16
TÜV component mark
HTB (DN 32–150, MOP 5)
TA Luft

Temperature Range

Standard: -10°C to +150°C; DVGW -20°C to +60°C
On request: -20°C to +250°C

Application Range

Liquids: Fluid group 1 and 2 in accordance with PED 2014/68/EU Article 13
Gases: Fluid group 1 and 2 in accordance with PED 2014/68/EU Article 13
Resistance to the flow medium must always be ensured.

Other product categories

Product finder

Start your inquiry quickly and easily
with our product finder.

von Scheven – Applications
Always a step ahead

News. Info. Trade fair dates.

All the latest news from von Scheven.

All news from von Scheven at a glance: In our news section, we provide information on current developments, product innovations, and exciting insights into our ball valve manufacturing facility. Additionally, you will find all important trade fair dates and events here, where you can experience von Scheven personally.